RangeActi9
Product nameDisbo iC60
product or component typeMiniature circuit-breaker
Device short nameIC60N
poles description2P
Number of protected poles2
[In] rated current16 A
Network typeAC
Trip unit technologyThermal-magnetic
Curve codeC
Breaking capacity10 kA Icu at <= 125 V DC conforming to EN/IEC 60947-2
6000 A Icn at 415 V AC 50/60 Hz conforming to EN/IEC 60898-1
36 kA Icu at 12...133 V AC 50/60 Hz conforming to EN/IEC 60947-2
20 kA Icu at 220...240 V AC 50/60 Hz conforming to EN/IEC 60947-2
10 kA Icu at 380...415 V AC 50/60 Hz conforming to EN/IEC 60947-2
6 kA Icu at 440 V AC 50/60 Hz conforming to EN/IEC 60947-2
Utilisation categoryCategory A conforming to EN/IEC 60947-2
Complementary
Network frequency50/60 Hz
[Ue] rated operational voltage400 V AC 50/60 Hz
Magnetic tripping limit8 x In +/- 20 %
[Ics] rated service breaking capacity27 kA 75 % conforming to EN/IEC 60947-2 - 12...133 V AC 50/60 Hz
15 kA 75 % conforming to EN/IEC 60947-2 - 220...240 V AC 50/60 Hz
7.5 kA 75 % conforming to EN/IEC 60947-2 - 380...415 V AC 50/60 Hz
4.5 kA 75 % conforming to EN/IEC 60947-2 - 440 V AC 50/60 Hz
6000 A 100 % conforming to EN/IEC 60898-1 - 415 V AC 50/60 Hz
6 kA 100 % conforming to EN/IEC 60947-2 - 100...133 V DC
Limitation class3 conforming to EN/IEC 60947-2
[Ui] rated insulation voltage500 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-2
Contact position indicatorYes
Control typeToggle
local signallingTrip indicator
mounting modeClip-on
mounting supportRail
9 mm pitches4
Height85 mm
Width36 mm
Depth78.5 mm
net weight0.25 kg
ColourWhite
Mechanical durability20000 cycles
Electrical durability10000 cycles
Provision for padlockingPadlockable
Connections - terminalsSingle terminal (top or bottom) 1…25 mm² rigid
Single terminal (top or bottom) 1…16 mm² flexible
Wire stripping length14 mm for top or bottom connection
Tightening torque2 N.m top or bottom
Earth-leakage protectionSeparate block
Environment
StandardsEN/IEC 60947-2
EN/IEC 60898-1
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree3 conforming to EN/IEC 60947-2
Tropicalisation2 conforming to IEC 60068-1
Relative humidity95 % at 55 °C
Ambient air temperature for operation-35…70 °C
ambient air temperature for storage-40…85 °C
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height3.6 cm
Package 1 Width7.4 cm
Package 1 Length9 cm
Package 1 Weight218 g
Unit Type of Package 2BB1
Number of Units in Package 26
Package 2 Height8.5 cm
Package 2 Width9.8 cm
Package 2 Length22 cm
Package 2 Weight1.356 kg
Unit Type of Package 3S03
Number of Units in Package 366
Package 3 Height30 cm
Package 3 Width30 cm
Package 3 Length40 cm

 

A9F44216, Acti9 iC60N 2P 16A AC Miniature Circuit breaker

42.00AEDPrice
    • Refunds will be issued to the original payment method used for the purchase.
    • Please allow 5-6 business days for the refund to appear in your account, depending on your financial institution.
    • Processing Time: Orders typically ship within 3-4  business days after payment is received.
    • Tracking Information: Once your order is shipped, you will receive a shipping confirmation email with tracking details. You can use this information to track your package online.
bottom of page